Select Page

LIGHT AND SOUND SIGNALING DEVICES FOR 503 WALL BOX

According to your needs, you can choose one among the following signaling devices:
1200/1: Double light indication with red and green colors and sound signal. It is activated with a call button a reset with a reset button.

1200/2: Flashing red light combined with a sound signal. It is designed to be activated by an external relay.

1200/3: Red light combined with a sound signal. It is activated with a call button a reset with a reset button.

1200/LC3: Signaling devices with red-green-white light and sound signal. It is used to indicate if the call originates from the room or the bathroom and when the nurse is present. It includes a room interface unit for the G99 system.

1200/1 – ACOUSTICAL AND OPTICAL EMERGENCY SIGNALING DEVICE WITH LOGICAL INTERLOCK

FOR HOSPITALS, WITH LOGICAL INTERLOCK

The device can be installed inside a standard box for 3 modules, both for wall o flush mounting. It creates an optical and acoustical signaling system with double alternate RED-GREEN lights with interlocked buttons.
It can be connected to the call system with LED LIGHTS. It satisfies the most recent prescriptions for hospitals, health care centers, nursing homes, etc.., by signaling outside of the room the call (RED light) or the presence of the nurses (GREEN light).

Art.1200/1
12-24V AC
Flush mounting inside a 503 wall box
Box = 1 pz

Tech Specs:
– Power Supply: 12-24VAC – through a safety transformer.
– Max power consumption: 6W
– LED lights: 12-24V 3W
DOES NOT ALLOW GENERAL AND ROOM RESET

1200/1 – Connection diagram

1200/2 – EMERGENCY OPTICAL AND ACOUSTICAL SIGNALING DEVICE

CAN BE CONNECTED TO A LED CALL SYSTEM (art.1200/.. o 1201/..)

Electronic optical/acoustical signaling device for an emergency call: the RED light is activated and the buzzer emits a sound.
The buzzer can be deactivated (With a jumper between the pins T1-T2).

Operation:
The device is activated/deactivated by opening/closing the external relay that is connected to the pins An-An. This device is thought to be used in combination with a call from a LED call system: the LED call systems are equipped with a relay with clean contacts that are closed when a call is active and this activates the signaling device as well. When the call is reset, the relay contacts are opened and the call is deactivated.
Since the 1200/2 is activated/deactivated by closing or opening the contacts of a relay/switch, it is perfectly suited to be used in combination with the following call systems:
– LED CALL SYSTEMS p/n 1200/.. or 1201/..;
– CONTROL UNITS FOR TEMPERATURE AND LIQUID LEVELS;
– CONTROL UNITS FOR GASES AND EXHAUST SMOKES;
– REMOTE OR LOCAL EMERGENCY SIGNALS, BOTH INCLUDED OR NOT IN SECURITY SYSTEMS.

Art.1200/2
12-24V AC
Flush mount for 503 wall box
Box = 1 pz

Tech specs:
– Power supply: 12-24VAC – through a safety transformer.
– VERY SIMPLE INTEGRATION WITH 1200/.. or 1201/.. LED CALL SYSTEMS
– Max power consumption: 2W
– Light signal: N°10 high intensity LED lights
– Sound signal: Piezo buzzer 60dB at 1m

1200/2 – Connection diagram

1200/3 – STANDALONE ACOUSTICAL/OPTICAL SIGNALING DEVICE

Electronic signaling device suitable for emergency signals with a red light and an intermittent sound.

Operation:
DEVICE DESIGNED FOR STANDALONE OPERATION

CALL BUTTON: activation of the optical and acoustical alarm
RESET BUTTON: resets the device

Fields of use:
Call systems in private or public settings (bathroom alarm, opening of secure doors, etc..) or for businesses (workshops, etc..) and wherever it is necessary to activate and reset an emergency signal with light and sound.

EXAMPLES OF USE:
– BATHROOM ALARM
– SIGNALS FOR THE STATE OF MACHINING IN MANUFACTURING PROCESSES
– DANGER SIGNALS
– ALARM OR MALFUNCTION SIGNALS
– SIGNALS FOR EMERGENCY EXITS
– REMOTE CALL OR EMERGENCY SIGNALS
– REMOTE SIGNALS FOR BURGLAR ALARMS

Art.1200/3
12-24V AC
Flush mount for 503 wall box
Box = 1 pz

Tech specs:
– Power supply: 12-24VAC – through a safety transformer. (Recommended: P/N 1115 for standalone use)
– Max power consumption: 2W
– Light signal: 10 high intensity red LEDs
– Sound signal: Buzzer rated at 60dB at 1m

1200/3 – Connection diagrams

1200/LC3 – OPTICAL/ACOUSTICAL SIGNALING DEVICE – INCLUDES ROOM INTERFACE FOR G99 CALL SYSTEM

This device is equipped with three different lights for the optical signals and has a buzzer for the sound signal. The three lights can indicate if the alarm is coming in example from the room or the bathroom and when the nurse is present in the room, providing assistance.
This device includes a room device for the G99 system and can be directly incorporated in it. Like the other room devices for the G99 call system, the room number associated to each 1200/LC3 in the system is automatically assigned by the master unit P/N 1600/G99 or P/N 1600/BIG (see diagrams).

Operation:
Room call button: It activates the optical/acoustical alarm by turning on the RED LED and the buzzer.
Bathroom call button: It activates the optical/acoustical alarm by turning on the WHITE LED and the buzzer.
Reset button: First push: resets the call, turns off the RED or WHITE LED and turns on the GREEN LED that indicates presence of the nurse in the room.
Reset button: Second push: turns off the GREEN LED and resets the call system.
The call button is always enabled.
The reset button is enabled only after the call button has been pushed.

This device is designed according to the DIN VDE 0834-1 specifications

Art.1200/LC3
12V AC
Flush mount for 503 wall box
Box = 1 pz

Tech specs:
– Power supply: 12VAC – through a safety transformer.
– Max power supply: 2W
– Light signal: high intensity red, green and white LEDs.
– Sound signal: Buzzer rated at 60db ad 1m.

1200/LC3 – Connection diagram